BELIMO UHB24Y-L ,IP20 - NEMA 1 ,Actuating force motor 50 N ,Nominal voltage AC/DC 24 V ,Power consumption in operation : 1 W ,Power consumption in rest position : 0.5 W ,Transformer sizing : 2 VA ,Control On/Off, Floating point ,Direction of motion motor : by electrical installation ,Weight : 0.24 lb [0.11 kg]
หมวดหมู่ : PRODUCTS ,  ELECTRICAL ,  BELIMO ,  NON FAIL-SAFE ACTUATORS , 
แบรนด์ : BELIMO distributor
Share
ผู้จำหน่าย Non Fail-Safe Actuators ยี่ห้อ BELIMO รุ่น UHB24Y-L ราคาถูก นำเข้าตรงจากโรงงานผลิต Linear actuator, 50 N, AC/DC 24 V, On/Off, Floating point, 122 s, Stroke 60 mm, IP20 Direction Of Motion Motor : by electrical installation ตัวแทนจำหน่ายและนำเข้า สินค้าอุตสาหกรรมในประเทศไทย
BELIMO UHB24Y-L Basic Non Fail-Safe modulating actuator สำหรับควบคุมแดมเปอร์ (dampers) ในแอพพลิเคชั่น HVAC เชิงพาณิชย์ทั่วไป
• Actuating force motor 50 N
• Nominal voltage AC/DC 24 V
• Control On/Off, Floating point
Technical data
Electrical data | |
Nominal voltage | AC/DC 24 V |
Nominal voltage frequency | 50/60 Hz |
Nominal voltage range | AC 19.2...28.8 V / DC 19.2...28.8 V |
Power consumption in operation | 1 W |
Power consumption in rest position | 0.5 W |
Transformer sizing | 2 VA |
Connection supply / control | Connector Plug (Cable-side connector socket not included in scope of delivery) |
Connection plug | Molex Mini-Fit Jr. 39303035 |
Parallel operation | Yes (note the performance data) |
Functional data | |
Actuating force motor | 50 N |
Direction of motion motor | by electrical installation |
Manual override | No |
Stroke | 60 mm |
Length of Stroke | Max. 60 mm, adjustable in 1 mm increments |
Stroke limitation | can be limited on both sides with mechanical end stops adjustable in 1 mm increments between 30...60mm |
Running Time (Motor) | 122 s / 100 mm |
Running time motor note | corresponds to 74 s / 60 mm |
Noise level, motor | 35 dB(A) |
Safety data | |
Protection class IEC/EN | III, Safety Extra-Low Voltage (SELV) |
Degree of protection IEC/EN | IP20 |
Degree of protection NEMA/UL | NEMA 1 |
Enclosure | UL Enclosure Type 1 |
EMC | CE according to 2014/30/EU |
Certification IEC/EN | IEC/EN 60730-1 and IEC/EN 60730-2-14 |
UL Approval | cURus according to UL60730-1A, UL60730-2-14 and CAN/CSA E60730-1 |
Type of action | Type 1 |
Rated impulse voltage supply / control | 0.8 kV |
Pollution degree | 2 |
Ambient humidity | Max. 95% RH, non-condensing |
Ambient temperature | -22...122°F [-30...50°C] |
Storage temperature | -40...176°F [-40...80°C] |
Weight | 0.24 lb [0.11 kg] |
Product features
Simple direct mounting
• The actuator can be directly connected with the application using the enclosed screws.
• The head of the gear rod is connected to the moving part of the ventilation application individually
on the mounting side.
High functional reliability
• The actuator is overload protected, requires no limit switches and automatically stops when
the end stop is reached.
Restriction 3-point controller
• For applications with 3-point open-loop control, a minimum pulse length of 1 sec. is
recommended to increase position accuracy.
• For applications with 3-point closed-loop control, a pulse length of 0.5 sec. is possible to